home Bangkokcable.com
Print this page section | main menu

300V 70C VAF
TIS 11-2531, TABLE 2 (2 CORE)
VAF CABLE

Construction
1. Conductor : Solid or concentric stranded annealed copper wires
2. Insulation : Polyvinyl chloride (PVC)
    Identification : Gray and Black color
3. Sheath : Polyvinyl chloride (PVC), White color
Application
For surface wiring, concealed wiring in wooden partition or above ceiling, embedded in plaster, dry location.

Conductor
Thickness
of
insulation



mm
Thickness
of
sheath



mm
Overall
diameter
Current rating
in air




A
Minimum
insulation
resistance
(at 70°C)


Mohm-km
Cable
weight
(Approx.)



kg/km
Standard
Length




m
Nominal
cross-
sectional
area
sq.mm
No.& dia.
of
wires

No./mm
lower
limit


mm
upper
limit


mm
0.5 1/0.80 0.6 0.9 3.6 x 5.6 4.4 x 6.8 7 0.0146 37 100/C
1 1/1.13 0.6 0.9 4.0 x 6.2 4.8 x 7.4 11 0.0115 50 100/C
1 7/0.40 0.6 0.9 4.0 x 6.4 5.0 x 7.8 11 0.0110 50 100/C
1.5 1/1.38 0.6 1.2 4.8 x 7.2 5.8 x 8.6 16 0.0100 70 100/C
1.5 7/0.50 0.6 1.2 4.9 x 7.4 6.0 x 9.2 16 0.0094 70 100/C
2.5 1/1.78 0.7 1.2 5.4 x 8.4 6.4 x 10.0 21 0.0092 100 100/C
2.5 7/0.67 0.7 1.2 5.6 x 8.8 6.8 x 10.5 21 0.0084 100 100/C
4 1/2.25 0.8 1.2 6.0 x 9.8 7.2 x 11.5 29 0.0086 140 100/C
4 7/0.85 0.8 1.2 6.2 x 10.0 7.6 x 12.0 29 0.0078 140 100/C
6 7/1.04 0.8 1.2 6.8 x 11.0 8.2 x 13.5 36 0.0066 200 100/C
10 7/1.35 0.9 1.2 8.0 x 13.5 9.4 x 16.0 51 0.0059 300 100/C
16 7/1.70 1.0 1.2 9.2 x 16.0 11.0 x 18.5 67 0.0053 440 100/C
25 7/2.14 1.2 1.4 11.0 x 19.5 13.0 x 22.5 91 0.0051 690 500/D
35 19/1.53 1.2 1.4 12.0 x 22.0 14.5 x 25.0 111 0.0043 900 500/D
 