home Bangkokcable.com
Print this page
section | main menu


Lead Free PVC Insulated Wire (UL 1007-LF) UL, CSA Approved PVC Wire



Description UL 1007-LF (CSA TR-64)
Rating 80 íC, 300V (UL) / 90 íC, 600V peak (CSA)
Standard UL Subject 758, CSA C22.2 No.127
Construction  
Marking

AWM E106028 STYLE 1007 LF ** AWG VW-1 BANGKOK CABLE  –F–
CSA LL68482 TYPE TR-64 90C FT1

 
 



Conductor
Insulation
thickness


Nominal
(mm)
Overall
diameter


Approx.
(mm)
Conductor
resistance
(at 20 íC)

Maximum
(ohm/km)
Mass

Approx.
(kg/km)
Standard length
Size


(AWG)

Construction


(No./mm)
Diameter


Approx.
(mm)

Coil

(m)

Bobbin

(m)

28
7/0.127
0.38
0.41
1.20
223.0
2.2
610
3,050
26
7/0.16
0.48
0.41
1.30
139.0
2.9
610
3,050
24
11/0.16
0.61
0.41
1.43
89.8
3.8
610
2,440
22
17/0.16
0.76
0.41
1.58
58.1
5.2
610
2,135
20
26/0.16
0.94
0.41
1.76
38.3
7.2
610
-
18
43/0.16
1.21
0.41
2.03
23.4
10.7
305
-
16
54/0.18
1.53
0.41
2.35
14.6
16.0
305
-
 
Note : 1. Standard for safety File No. : UL : E106028, CSA : LL68482
    2. BCC specification No. : ELA 001/0108
    3. ** : Size of conductor
     

Copyright 2005 . www.bangkokcable.com