home Bangkokcable.com
Print this page
section | main menu

0.6/1 kV XLPE/LSHF
IEC 60502 (1 CORE)
0.61/1 kV FR/XLPE/LSHF(1 CORE) CABLE

Construction
1. Conductor : Concentric stranded or compact stranded annealed copper wires
2. Insulation : Cross-linked polyethylene (XLPE) Natural color
3. Sheath : Low smoke halogen free thermoplastic compound (LSHF)
Application
The cable are specially designed to widely used in crowded buildings and structure
where flame retardant and low smoke halogen free properties are required.

Conductor
Thickness
of
insulation
(Nominal)

mm
Thickness
of
Sheath
(Nominal)

mm
Overall
diameter
(Approx.)


mm
Maximum
conductor
resistance
(at 20°C)

Ohm/km
Current
rating
in air


A
Cable
weight
(Approx.)


kg/km
Standard
Length



m
Nominal
cross-
sectional
area
sq.mm
Strands




Diameter
(Approx.)


mm
1.5 7/0.52 1.56 0.7 1.4 6.5 12.1 27 50 500/D
2.5 7/0.67 2.01 0.7 1.4 7.0 7.41 36 60 500/D
4 7/0.85 2.55 0.7 1.4 7.5 4.61 48 80 500/D
6 7/1.04 3.12 0.7 1.4 8.0 3.08 61 100 500/D
10 6 3.72 0.7 1.4 8.5 1.83 82 150 500/D
16 6 4.69 0.7 1.4 9.5 1.15 110 210 500/D
25 6 5.90 0.9 1.4 11.5 0.727 145 320 500/D
35 6 6.95 0.9 1.4 12.5 0.524 180 420 500/D
50 6 8.33 1.0 1.4 14.0 0.387 220 560 500/D
70 12 9.73 1.1 1.4 15.5 0.268 280 770 500/D
95 15 11.43 1.1 1.5 17.5 0.193 345 1050 500/D
120 18 12.95 1.2 1.5 19.5 0.153 400 1300 500/D
150 18 14.27 1.4 1.6 21.5 0.124 460 1600 500/D
185 30 15.98 1.6 1.6 23.5 0.0991 530 2000 500/D
240 34 18.47 1.7 1.7 26.5 0.0754 630 2600 500/D
300 34 20.68 1.8 1.8 29.0 0.0601 725 3230 500/D
400 53 23.39 2.0 1.9 32.5 0.0470 840 4100 500/D
500 53 26.67 2.2 2.0 36.5 0.0366 1000 5260 500/D
630 53 30.22 2.4 2.2 41.0 0.0283 1170 6780 400/D
800 53 34.00 2.6 2.3 45.5 0.0221 1340 8630 400/D

Copyright 2005 Ó. www.bangkokcable.com
All Rights Reserved. Design & Update by :: TEAM IT bangkokcable.com