home Bangkokcable.com
Print this page
section | main menu

0.6/1 kV CV-VP
IEC 60502 (2 CORE)

0.61/1 kV CV-VP(2 CORE) CABLE
Construction
1. Conductor : Concentric stranded or compact stranded annealed copper wires
2. Insulation : Cross-linked polyethylene (XLPE)
    Identification : Red and Black color
3. Filler : Polypropylene (Non-hygroscopic material)
4. Binding tape : Polyester / Spunbond tape
5. Sheath : Polyvinyl chloride (PVC), Vermin proof
    Option : Steel wire tape armour
Application
For general purpose power distribution in dry or wet location, installation exposed,
in conduit or duct at the area which have been required repellent effect to rodents
or vermin.

Conductor
Thickness
of
insulation


mm
Thickness
of
Sheath


mm
Overall
diameter
(Approx.)


mm
Maximum
conductor
resistance
(at 20°C)

Ohm/km
Current
rating
in air


A
Cable
weight
(Approx.)


kg/km
Standard
Length



m
Nominal
cross-
sectional
area
sq.mm
Strands




2.5 7/0.67 0.7 1.8 11.6 7.41 34 150 500/D
4 7/0.85 0.7 1.8 12.8 4.61 44 190 500/D
6 7/1.04 0.7 1.8 14.0 3.08 57 245 500/D
10 7 0.7 1.8 15.3 1.83 77 335 500/D
16 7 0.7 1.8 17.5 1.15 100 470 500/D
25 7 0.9 1.8 20.5 0.727 135 695 500/D
35 7 0.9 1.8 23.0 0.524 165 915 500/D
50 7 1.0 1.8 26.0 0.387 205 1195 500/D
70 18 1.1 1.8 29.5 0.268 255 1640 500/D
95 18 1.1 2.0 33.5 0.193 315 2240 500/D
120 18 1.2 2.1 37.5 0.153 365 2795 300/D
150 18 1.4 2.2 41.0 0.124 415 3425 300/D
185 34 1.6 2.3 46.0 0.0991 485 4270 200/D
240 34 1.7 2.5 52.5 0.0754 580 5570 200/D
300 34 1.8 2.7 57.5 0.0601 675 6910 150/D
400 55 2.0 2.9 64.5 0.0470 790 8770 150/D

Copyright 2005 . www.bangkokcable.com
All Rights Reserved. Design & Update by :: TEAM IT bangkokcable.com