1.8/3(3.6) kV CV-SWA (CE optional)*
IEC 60502-1 (3 CORE)
CV-SWA(3 CORE) 1.8/(3.6)kV CABLE

Construction
1. Conductor : Compact round stranded annealed copper wires
2. Insulation : Cross-linked polyethylene (XLPE)
3. Filler : Polypropylene (Non-hygroscopic material)
4. Binding tape : Polyester / Spunbond tape
5. Inner sheath : Polyvinyl chloride (PVC), ( Optional : PE )*
6. Armour : Galvanized steel wires
7. Binding tape : Polyester / Spunbond tape
8. Outer sheath : Polyvinyl chloride (PVC), ( Optional : PE )*
Application
For general purpose power distribution in dry and wet location, installation in exposed,
in conduit or duct or direct burying in ground.

Conductor
Thickness
of
Insulation
(Nominal)


mm
Thickness
of
Inner Sheath
(Aprox.)


mm
Daimeter
of
Armour
wires
(Nominal )

mm
Thickness
of
Outer
Sheath
(Nominal)

mm
Overall
diameter
(Approx.)



mm
Maximum
DC.
Conductor
resistance
at 20°C

ohm/km
Current
rating
in air



A
Cable
weigth
(Approx.)



kg/km
Standard
packing
length



m
Size



mm2
Number
of wires
(Min.)



Diameter
(Approx.)



mm
10 6 3.72 2.0 1.0 1.6 1.8 30 1.83 69 1500 500
16 6 4.69 2.0 1.0 1.6 1.9 32 1.15 92 1820 500
25 6 5.90 2.0 1.0 1.6 1.9 35 0.727 120 2280 500
35 6 6.95 2.0 1.0 2.0 2.0 38 0.524 150 2970 500
50 6 8.33 2.0 1.2 2.0 2.2 42 0.387 180 3650 500
70 12 9.73 2.0 1.2 2.0 2.3 46 0.268 225 4530 500
95 15 11.43 2.0 1.2 2.5 2.4 51 0.193 275 6040 300
120 18 12.95 2.0 1.4 2.5 2.5 55 0.153 315 7200 300
150 18 14.27 2.0 1.4 2.5 2.6 58 0.124 360 8300 300
185 30 15.98 2.0 1.4 2.5 2.8 62 0.0991 410 9840 250
240 34 18.47 2.0 1.6 2.5 3.0 69 0.0754 480 12200 200
300 34 20.68 2.0 1.6 2.5 3.1 74 0.0601 550 14500 150
400 53 23.39 2.0 1.6 3.15 3.4 82 0.0470 625 18700 150
 

Copyright 2005 . www.bangkokcable.com