home Bangkokcable.com
Print this page
section | main menu

1.8/3(3.6) kV CV-AWA (CE optional)*
IEC 60502-1 (1 CORE)
CV-AWA(1 CORE) 1.8/(3.6)kV CABLE

Construction
1. Conductor : Compact round stranded annealed copper wires
2. Insulation : Cross-linked polyethylene (XLPE)
3. Binding tape : Polyester / Spunbond tape
4. Inner sheath : Polyvinyl chloride (PVC), ( Optional : PE )
5. Armour : Hard-drawn aluminium wires
6. Binding tape : Polyester / Spunbond tape
7. Outer sheath : Polyvinyl chloride (PVC), ( Optional : PE )*
Application
For general purpose power distribution in dry and wet location, installation in exposed,
in conduit or duct or direct burying in ground.

Conductor
Thickness
of
Insulation
(Nominal)


mm
Thickness
of
Inner Sheath
(Approx.)


mm
Daimeter
of
Armour
wires
(Nominal )

mm
Thickness
of
Outer
Sheath
(Nominal)

mm
Overall
diameter
(Approx.)



mm
Maximum
DC.
Conductor
resistance
at 20°C

ohm/km
Current rating
in air
 

A

Cable
weigth
(Approx.)



kg/km
Standard
packing
length



m
Size



mm2
Number
of wires
(Min.)



Diameter
(Approx.)



mm
10 6 3.72 2.0 1.0 0.8 1.4 17 1.83 82 280 500
16 6 4.69 2.0 1.0 1.25 1.5 19 1.15 105 410 500
25 6 5.90 2.0 1.0 1.25 1.5 20 0.727 140 530 500
35 6 6.95 2.0 1.0 1.25 1.5 21 0.524 170 640 500
50 6 8.33 2.0 1.0 1.25 1.6 23 0.387 205 800 500
70 12 9.73 2.0 1.0 1.6 1.7 25 0.268 260 1080 500
95 15 11.43 2.0 1.0 1.6 1.7 27 0.193 320 1380 500
120 18 12.95 2.0 1.0 1.6 1.8 29 0.153 370 1670 500
150 18 14.27 2.0 1.0 1.6 1.8 30 0.124 420 1970 500
185 30 15.98 2.0 1.0 1.6 1.9 32 0.0991 485 2380 500
240 34 18.47 2.0 1.0 1.6 1.9 35 0.0754 575 3000 500
300 34 20.68 2.0 1.0 2.0 2.0 38 0.0601 665 3750 500
400 53 23.39 2.0 1.2 2.0 2.2 42 0.0470 775 4680 500
500 53 26.67 2.2 1.2 2.0 2.3 46 0.0366 900 5900 300
630 53 30.22 2.4 1.2 2.5 2.4 51 0.0283 1045 7610 300
800 53 34.00 2.6 1.4 2.5 2.6 57 0.0221 1190 9590 250
 

Copyright 2005 Ó. www.bangkokcable.com
All Rights Reserved. Design & Update by :: TEAM IT bangkokcable.com