home Bangkokcable.com
Print this page
section | main menu

12/20(24) kV CV (CE optional)*
IEC 60502-2 (3 CORE)
CV(3 CORE) 12/20(24)kV CABLE

Construction
1. Conductor : Compact round stranded annealed copper wires
2. Conductor screen : Semi-conductive Cross-linked polyethylene (XLPE) compound
3. Insulation : Cross-linked polyethylene (XLPE)
4. Insulation screen : Semi-conductive Cross-linked polyethylene (XLPE) compound
5. Metallic screen : Copper tape
6. Filler : Polypropylene (Non-hygroscopic material)
7. Binding tape : Polyester / Spunbond tape
8. Sheath : Polyvinyl chloride (PVC), ( Optional : PE )*
Application
For general purpose power distribution in dry and wet location, installation in exposed,
in conduit or duct or direct burying in ground.

Conductor
Insulation
thickness
nominal



mm
Diameter
over
insulation
(Approx.)


mm.
Sheath
thickness
nominal



mm
Overall
diameter
(Approx.)



mm
Maximum
DC.
Conductor
resistance
at 20°C

ohm/km
Current
rating
in air



A
Cable
weight
(Approx.)



kg/km
Standard
length




m
Size



mm2
Number
of wires
(Min.)



Diameter
(Approx.)



mm
35 6 6.95 5.5 19.5 2.6 54 0.524 180 3280 500
50 6 8.33 5.5 20.9 2.7 57 0.387 215 3875 500
70 12 9.73 5.5 22.3 2.8 61 0.268 265 4705 500
95 15 11.43 5.5 24.0 2.9 65 0.193 325 5760 300
120 18 12.95 5.5 25.5 3.0 68 0.153 370 6757 300
150 18 14.27 5.5 26.9 3.1 71 0.124 420 7810 300
185 30 15.98 5.5 28.6 3.3 76 0.0991 485 9240 250
240 34 18.47 5.5 31.7 3.4 83 0.0754 575 11490 200
300 34 20.68 5.5 33.9 3.6 88 0.0601 660 13745 150

Copyright 2005 Ó. www.bangkokcable.com