home Bangkokcable.com
Print this page
section | main menu

8.7/15(17.5) kV CV (CE optional)*
IEC 60502-2 (3 CORE)
CV(3 CORE) 8.7/15(17.5)kV CABLE

Construction
1. Conductor : Compact round stranded annealed copper wires
2. Conductor screen : Semi-conductive Cross-linked polyethylene (XLPE) compound
3. Insulation : Cross-linked polyethylene (XLPE)
4. Insulation screen : Semi-conductive Cross-linked polyethylene (XLPE) compound
5. Metallic screen : Copper tape
6. Filler : Polypropylene (Non-hygroscopic material)
7. Binding tape : Polyester / Spunbond tape
8. Sheath : Polyvinyl chloride (PVC), ( Optional : PE )*
Application
For general purpose power distribution in dry and wet location, installation in exposed,
in conduit or duct or direct burying in ground.

Conductor
Insulation
thickness
nominal



mm
Diameter
over
insulation
(Approx.)


mm.
Sheath
thickness
nominal



mm
Overall
diameter
(Approx.)



mm
Maximum
DC.
Conductor
resistance
at 20°C

ohm/km
Current
rating
in air



A
Cable
weight
(Approx.)



kg/km
Standard
length




m
Size



mm2
Number
of wires
(Min.)



Diameter
(Approx.)



mm
25 6 5.90 4.5 16.4 2.4 46 0.727 145 2450 500
35 6 6.95 4.5 17.5 2.5 49 0.524 175 2895 500
50 6 8.33 4.5 18.8 2.6 52 0.387 210 3465 500
70 12 9.73 4.5 20.2 2.7 56 0.268 265 4275 500
95 15 11.43 4.5 21.9 2.8 60 0.193 320 5305 300
120 18 12.95 4.5 23.5 2.9 63 0.153 370 6270 300
150 18 14.27 4.5 24.8 3.0 66 0.124 420 7305 300
185 30 15.98 4.5 26.5 3.1 70 0.0991 480 8670 250
240 34 18.47 4.5 29.6 3.3 78 0.0754 570 10905 200
300 34 20.68 4.5 31.8 3.4 83 0.0601 655 13080 150

Copyright 2005 Ó. www.bangkokcable.com
All Rights Reserved. Design & Update by :: TEAM IT bangkokcable.com