home Bangkokcable.com
Print this page
section | main menu

6/10(12) kV CV (CE optional)*
IEC 60502-2 (3 CORE)
CV(3 CORE) 6/10(12)kV CABLE

Construction
1. Conductor : Compact round stranded annealed copper wires
2. Conductor screen : Semi-conductive Cross-linked polyethylene (XLPE) compound
3. Insulation : Cross-linked polyethylene (XLPE)
4. Insulation screen : Semi-conductive Cross-linked polyethylene (XLPE) compound
5. Metallic screen : Copper tape
6. Filler : Polypropylene (Non-hygroscopic material)
7. Binding tape : Polyester / Spunbond tape
8. Sheath : Polyvinyl chloride (PVC), ( Optional : PE )*
Application
For general purpose power distribution in dry and wet location, installation in exposed,
in conduit or duct or direct burying in ground.

Conductor
Insulation
thickness
nominal



mm
Diameter
over
insulation
(Approx.)


mm.
Sheath
thickness
nominal



mm
Overall
diameter
(Approx.)



mm
Maximum
DC.
Conductor
resistance
at 20°C

ohm/km
Current
rating
in air



A
Cable
weight
(Approx.)



kg/km
Standard
length




m
Size



mm2
Number
of wires
(Min.)



Diameter
(Approx.)



mm
16 6 4.69 3.4 12.9 2.1 38 1.15 110 1645 500
25 6 5.90 3.4 14.1 2.2 41 0.727 140 2065 500
35 6 6.95 3.4 15.2 2.3 43 0.524 175 2490 500
50 6 8.33 3.4 16.6 2.4 47 0.387 210 3035 500
70 12 9.73 3.4 18.0 2.5 50 0.268 260 3815 500
95 15 11.43 3.4 19.7 2.6 54 0.193 315 4810 500
120 18 12.95 3.4 21.2 2.7 58 0.153 365 5750 300
150 18 14.27 3.4 22.5 2.8 61 0.124 415 6760 300
185 30 15.98 3.4 24.2 2.9 65 0.0991 475 8095 250
240 34 18.47 3.4 27.3 3.1 72 0.0754 570 10270 200
300 34 20.68 3.4 29.5 3.3 78 0.0601 650 12440 200

Copyright 2005 Ó. www.bangkokcable.com
All Rights Reserved. Design & Update by :: TEAM IT bangkokcable.com