1.8/3(3.6) kV CV (CE optional)* IEC 60502-1 (1 CORE) ![]() |
||||||
![]() |
||||||
| 1. Conductor | : Compact round stranded annealed copper wires | |||||
| 2. Insulation | : Cross-linked polyethylene (XLPE) | |||||
| 3. Binding tape | : Polyester / Spunbond tape | |||||
| 4. Metallic screen | : Copper tape | |||||
| 5. Binding tape | : Polyester / Spunbond tape | |||||
| 6. Sheath | : Polyvinyl chloride (PVC), ( Optional : PE )* | |||||
![]() |
||||||
| For general purpose power distribution in dry and wet location, installation in exposed, in conduit or duct or direct burying in ground. |
||||||
| Conductor |
Thickness of Insulation (Nominal) mm |
Thickness of Sheath (Nominal) mm |
Overall diameter (Approx.) mm |
Maximum DC. Conductor resistance at 20°C ohm/km |
Current rating in air A |
Cable weigth (Approx.) kg/km |
Standard packing length m |
||
|---|---|---|---|---|---|---|---|---|---|
| Size mm2 |
Number of wires (Min.) |
Diameter (Approx.) mm |
|||||||
| 10 | 6 | 3.72 | 2.0 | 1.4 | 13 | 1.83 | 93 | 240 | 500 |
| 16 | 6 | 4.69 | 2.0 | 1.4 | 14 | 1.15 | 120 | 310 | 500 |
| 25 | 6 | 5.90 | 2.0 | 1.4 | 15 | 0.727 | 160 | 420 | 500 |
| 35 | 6 | 6.95 | 2.0 | 1.4 | 16 | 0.524 | 195 | 530 | 500 |
| 50 | 6 | 8.33 | 2.0 | 1.4 | 18 | 0.387 | 235 | 670 | 500 |
| 70 | 12 | 9.73 | 2.0 | 1.5 | 20 | 0.268 | 295 | 900 | 500 |
| 95 | 15 | 11.43 | 2.0 | 1.5 | 21 | 0.193 | 365 | 1180 | 500 |
| 120 | 18 | 12.95 | 2.0 | 1.6 | 23 | 0.153 | 420 | 1450 | 500 |
| 150 | 18 | 14.27 | 2.0 | 1.6 | 24 | 0.124 | 480 | 1740 | 500 |
| 185 | 30 | 15.98 | 2.0 | 1.7 | 26 | 0.0991 | 555 | 2130 | 500 |
| 240 | 34 | 18.47 | 2.0 | 1.8 | 29 | 0.0754 | 660 | 2740 | 500 |
| 300 | 34 | 20.68 | 2.0 | 1.8 | 32 | 0.0601 | 760 | 3370 | 500 |
| 400 | 53 | 23.39 | 2.0 | 1.9 | 35 | 0.0470 | 880 | 4240 | 500 |
| 500 | 53 | 26.67 | 2.2 | 2.0 | 39 | 0.0366 | 1020 | 5400 | 300 |
| 630 | 53 | 30.22 | 2.4 | 2.2 | 43 | 0.0283 | 1170 | 6900 | 300 |
| 800 | 53 | 34.00 | 2.6 | 2.3 | 48 | 0.0221 | 1325 | 8800 | 250 |
|