home Bangkokcable.com
Print this page
section | main menu

8.7/15(17.5) kV CV (CE optional)*
IEC 60502-2 (1 CORE)
CV(1 CORE) 8.7/15(17.5)kV CABLE

Construction
1. Conductor : Compact round stranded annealed copper wires
2. Conductor screen : Semi-conductive Cross-linked polyethylene (XLPE) compound
3. Insulation : Cross-linked polyethylene (XLPE)
4. Insulation screen : Semi-conductive Cross-linked polyethylene (XLPE) compound
5. Metallic screen : Copper wires and copper contact tape
6. Binding tape : Polyester / Spunbond tape
7. Sheath : Polyvinyl chloride (PVC), ( Optional : PE )*
Application
For general purpose power distribution in dry and wet location, installation in exposed,
in conduit or duct or direct burying in ground.

Conductor
Insulation
thickness
nominal



mm
Diameter
over
insulation
(Approx.)


mm.
Sheath
thickness
nominal



mm
Overall
diameter
(Approx.)



mm
Maximum
DC.
Conductor
resistance
at 20°C

ohm/km
Current
rating
in air



A
Cable
weight
(Approx.)



kg/km
Standard
length




m
Size



mm2
Number
of wires
(Min.)



Diameter
(Approx.)



mm
25 6 5.90 4.5 16.4 1.7 25 0.727 170 740 500
35 6 6.95 4.5 17.5 1.7 26 0.524 205 855 500
50 6 8.33 4.5 18.8 1.7 27 0.387 245 1005 500
70 12 9.73 4.5 20.2 1.8 29 0.268 305 1245 500
95 15 11.43 4.5 21.9 1.8 31 0.193 375 1530 500
120 18 12.95 4.5 23.5 1.9 33 0.153 435 1810 500
150 18 14.27 4.5 24.8 1.9 34 0.124 495 2150 500
185 30 15.98 4.5 26.5 2.0 36 0.0991 565 2545 500
240 34 18.47 4.5 29.6 2.1 39 0.0754 675 3255 500
300 34 20.68 4.5 31.8 2.2 42 0.0601 775 3900 500
400 53 23.39 4.5 34.5 2.3 45 0.0470 900 4755 500
500 53 26.67 4.5 37.8 2.4 49 0.0366 1050 5965 300
630 53 30.22 4.5 41.4 2.5 52 0.0283 1220 7415 300
800 53 34.00 4.5 45.2 2.6 56 0.0221 1400 9195 250

Copyright 2005 Ó. www.bangkokcable.com
All Rights Reserved. Design & Update by :: TEAM IT bangkokcable.com