home Bangkokcable.com
Print this page
section | main menu

69 kV CE
IEC 60840


Construction
1. Conductor : Compact round stranded annealed copper wires
2. Conductor screen : Semi-conductive tape with extruded Semi-conductive XLPE compound
3. Insulation : Cross-linked polyethylene (XLPE)
4. Insulation screen : Semi-conductive XLPE compound
5. Water blocking tape : Semi-conductive water blocking tape
6. Metallic screen : Copper wires and copper contact tape
7. Water blocking and Cushioning tape : Non-conductive water blocking tape
8. Radial water barrier : Copolymer aluminium tape
9. Sheath : Polyethylene ( Optional : with RIB )
Application
Preferably laid in substations, factories and urban area. The cable shall be suitable for use in ducts, trays and direct burial in ground, subjected to immerse in water all time.
 
Conductor
Insulation
thickness
nominal



mm
Diameter
over
insulation
nominal


mm.

Cross-
Sectional
area of
Screen

mm2

Sheath
thickness
nominal



mm
Overall
diameter
(Approx.)



mm
Maximum
DC.
Conductor
resistance


ohm/km
Conductor
to screen
capacitance
nominal


mF/km
Ampacition
in free air
at 40°C
ambient


A
Cable
weight
(Approx.)



kg/km
Standard
length




m

Size
 



mm2

Number
of wires
(Min.)


Diameter
(Approx.)



mm

240

34 18.47 11.0 44.5 120 3.5 63 0.0754 0.195 675 5750 500
300 34 20.68 11.0 46.5 120 3.5 65 0.0601 0.211 775 6450 500
400 53 23.39 11.0 49.5 120 3.5 68 0.0470 0.226 895 7395 500
500 53 26.67 11.0 52.5 120 3.5 71 0.0366 0.249 1040 8620 500
630 53 30.22 11.0 56.5 120 3.5 75 0.0283 0.267 1205 10190 300
800 53 34.00 11.0 60.0 120 3.5 79 0.0221 0.293 1380 12100 300

Copyright 2005 Ó. www.bangkokcable.com